PVC Pressure Rating

Up Feedback Contents Search Terms of Use

 

D.A. Fehr Home
Up

George Fischer PVC Schedule 40 Pressure Rating

gflogo.jpg (29480 bytes)

Nominal Size

Outside Dia.

Wall

DR=D/t

73ºF f=1.00 S=2000

80ºF f=0.88 S=1760

90ºF f=0.75 S=1500

100ºF f=0.62 S=1240

110ºF f=0.50 S=1000

120ºF f=0.40 S=800

130ºF f=0.30 S=600

140ºF f=0.22 S=440

D

t

P

P

P

P

P

P

P

P

1/8 0.405 0.068 5.956 810 713 607 502 405 324 243 178
¼ 0.540 0.088 6.136 780 686 585 484 390 312 234 172
3/8 0.675 0.091 7.418 620 516 465 384 310 248 186 136
½ 0.840 0.109 7.706 600 528 450 372 300 240 180 132
¾ 1.050 0.113 9.292 480 422 360 298 240 192 144 106
1 1.315 0.133 9.887 450 396 338 279 225 180 135 90
1.660 0.140 11.857 370 326 278 229 185 148 111 81
1.900 0.145 13.103 330 290 248 205 165 132 99 73
2 2.375 0.154 15.422 280 246 210 174 140 112 84 62
2.875 0.203 14.162 300 264 225 186 150 120 90 66
3 3.500 0.216 16.204 260 229 195 161 130 104 78 57
4.000 0.225 17.699 240 211 180 149 120 96 72 53
4 4.500 0.237 18.987 220 194 165 136 110 88 66 48
5 5.563 0.258 21.560 190 167 143 118 95 76 57 42
6 6.625 0.280 23.661 180 158 135 112 90 72 54 40
8 8.625 0.322 26.785 160 141 120 99 80 64 48 35
10 10.750 0.365 29.452 140 124 105 87 70 56 42 31
12 12.750 0.406 31.404 130 116 99 82 66 53 39 29

1) Figures for Pressure Rating at 73ºF are rounded off from actual calculated values, and are the same as found in  ASTM D-1785.  Pressure Ratings for other temperatures are calculated from 73ºF values.

2) Pressure Rating values are for PVC pipe, and for most sizes are calculated from the experimentally determined Long-Term Strength of PVC extrusion compounds.  Because molding compounds may differ in Long-Term Strength and elevated temperature properties from pipe compounds, piping systems consisting of extruded pipe and molded fittings may have lower pressure ratings from those shown here, particularly at the higher temperatures.  Caution should be exercised in design of systems operating above 100ºF.

3) The pressure ratings given are for solvent-cemented systems.  When adding valves, or other components, the system must be derated to the rating of the lowest component.  (Pressure ratings: molded or cut threads are rated at 50% of solvent-cemented systems; for valves, see manufacturer's recommendations.)